Permit: T05PL01631

Parcel: 11943001A


Addresses:

1655 W AJO WY #083

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Date Description Inspector Results Comments
03/27/2006 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection :*
02/28/2006 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*
GAUGE ON 0 - CHECK FOR LEAKS
PRESSURE TEST OF MOBILE HOME & YARD PIPING REQUIRED
MOBILE HOME RATED GAS FLEX REQUIRED
AGA RATED GAS SHUT OFF VALVES REQUIRED
EXTEND FLUE PIPING TO 3' ABOVE SWAMP COOLER WITH DOUBLE WALL TYPE B VENT
PROVIDE 2 - 10"X10" OPENINGS IN DOOR TO WATER HEATER FOR COMBUSTION AIR.
RECALL FOR INSPECTINO WHEN READY.