Permit: T05PL01430

Parcel: 117042630


Addresses:

222 E 5TH ST

Inspection Status: Denied

Inspection History: PLUMBING - ROOF DRAINS

Date Description Inspector Results Comments
09/12/2005 PLUMBING - ROOF DRAINS Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PROVIDE CITY APPROVED PLAN FOR ROOF DRAINS. THIS ROOF IS APP. 75' X 150' WITH 3-4" DRAINS ONLY ON A 6" DRAIN SYSTEM AND 2-4" DRAINS ONLY ON A 4" DRAIN SYSTEM. THERE IS NO OVERFLOW DRAINAGE, SCUPPERS, OR GUTTER SYSTEM. ROOF HAS PARAPIT ON ALL SIDES
2) PROVIDE LONG RADIUS DRAINAGE FITTINGS
3) SUPPORT ALL PIPING AT CHANGES OF DIRECTION AND AT BOTH ENDS OF HORIZONTAL PIPING AT JOINTS
4) PROVIDE AIR OR WATER TEST ON SYSTEM
09/09/2005 PLUMBING - ROOF DRAINS Not ready for Inspection IVRS - Inspection :*
1) PLEASE LEAVE A NAME AND A CONTACT NUMBER WHEN SCHEDULING THIS INSPECTION
2) I FOUND THE PERMIT BUT NOT THE PLUMBER