Permit: T05PL01170

Parcel: 11943001A


Addresses:

1655 W AJO WY


Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Permit Number - T05PL01170

Inspection Description - PLUMBING - GAS PRESSURE TEST

Inspection Status - Approved

Date Description Inspector Results Comments
07/26/2005 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection :*
1) ALL CORRECTIONS HAVE BEEN MADE
07/22/2005 PLUMBING - GAS PRESSURE TEST Partial Approval IVRS - Inspection :*
1) B-1 VENT PIPE INCORRECT
07/20/2005 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) SHALL PROVIDE A FULL SIZE 3/4" T & P DRAIN AT WATER HTR
2) SHALL PROVIDE ONE 10 X 10 LOUVER GRILL ON WATER HTR DOOR LOCATED 12" BELOW CEILING
3) SHALL EXTEND WATER HTR FLU VENT AND TERMINATE 3' ABOVE COOLER
4) SHALL REMOVE MECHANICAL TAPE ON DBL WALL FLU VENT AT APPLIANCE COLLAR AT WATER HTR AND PROVIDE (3) SHEET METAL SCREWS PER JOINT
5) OK TO BACKFILL TRENCH
6) GAS PRESSURE TEST IS OK
07/15/2005 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
See detailed listing on site.| 999* UNIT # 271 1) USE LISTED MOBILE HOME FLEX CONNECTOR AT MOBILE HOME. 2) USE PRESSURE GAUGE THAT RENDS 19 1/10 LB INCREMENTS. 3) PROVIDE ACCESS TO FURNACE AND ANY OTHER GAS APPLIANCES.