Permit: T05PL01125

Parcel: 138231850

Inspection Status: Denied

Inspection History: PLUMBING - GAS PRESSURE TEST

Date Description Inspector Results Comments
07/14/2005 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) SHALL PROVIDE 2-10 X 10 MINIMUM LOUVER GRILLS LOCATED 12" BELOW CEILING AND 12" ABOVE FLOOR ON MECH. ROOM DOOR FOR COMBUSTION AIR
2) SHALL PROVIDE (3) SHEET METAL SCREWS PER JOINT FOR WATER HTR FLU VENT AND AT APPLIANCE COLLAR
3) SHALL PLUG AND REPLACE GAS SHUT OFF VALVE WITH AGA OR CSA VALVE AND PLUG THE END IF NO APPLIANCE IS AVAILABLE AT TIME OF INSPECTION
4) SHALL MAINTAIN MINIMUM OF 12" OF COVER FOR GAS LINE.
SOME AREAS APPEAR TO BE SHALLOW
07/14/2005 PLUMBING - GAS PRESSURE TEST Approved