Permit: T05PL00969

Parcel: 120082150


Addresses:

327 W ILLINOIS ST

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Date Description Inspector Results Comments
06/20/2005 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection :* 15 PSI TEST IS OK. RELOCATE GAS SHUT OFF VALVE @ WATER HEATER BEFORE THE FLEX CONNECTOR. PROVIDE DOUBLE WALL VENT PIPE & CAP ON WATER HEATER VENT. PROVIDE MIN 1 " CLEARANCE AT ROOF PENETRATION. PROVIDE T & P RELIEF DRAIN PIPE. RECALL FOR FINAL INSPECTION.
06/15/2005 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
See detailed listing on site.| 999* 1) SHALL PROVIDE AGA OF CSA APPROVED SHUT OFF VALVES @ ALL APPLIANCES. 2) SHALL PROVIDE FLU VENT AND CAP MIN OF 5' O" FOR WATER HTR. 3) SHALL PROVIDE A T & P VALVE & DRAIN TO DAYLIGHT FOR WATER HTR 4) GAS LINE FROM METER TO HOUSE SERVICE IS OK TO BACKFILL.
06/09/2005 PLUMBING - GAS PRESSURE TEST Partial Approval IVRS - Inspection :*
1) 1" SWITCH COAT FROM METER TO STUB UP AT BLDG 10 PSI AIR TEST OK TO COVER
2) WILL NEED TO SEE FULL GAS SYSTEM TEST AT FUTURE DATE
06/08/2005 PLUMBING - GAS PRESSURE TEST Not ready for Inspection IVRS - Inspection :* 1) I KNOCKED SEVERAL TIMES- I COULD HEAR SOMEONE YELLING INSIDE-BUT ON ONE CAME TO THE DOOR.