Permit: T05PL00968

Parcel: 14023055A


Addresses:

5713 S SOUTHLAND BL

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
04/07/2006 PLUMBING - FINAL Approved IVRS - Inspection :*
06/13/2005 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999* 1) SHALL EXTEND T & P DRAINS TO DAYLIGHT FULL SIZE 3/4" FOR WATER HTR. DO NOT USE A FLEX LINE. 2) SHALL PROVIDE ( 3) SHEET METAL SCREWS PER JOINT @ WATER HTR FLU VENT. 3) SHALL PROVIDE COMBUSTION RELIEF MIN 10'' X 10" LOUVER GRILLS LOCATED 12" ABOVE FLOOR AND 12" BELOW CEILINGS FOR WATER HTR ROOM AND FURNACE ROOM. THESE GRILLS MAY BE LOCATED ON THE DOOR. 4) SHALL LOCATE GAS SHUT OFF VALVE MIN 3' _ 0" FROM REGULATOR @ WATER HEATER @ SMALL UNIT. 5) SHALL EXTEND FURNACE FLU VENT MIN OF 2" ABOVE COOLER. 6) SHALL PROVIDE FLU VENT CAP FOR WATER HTR FRONT UNIT.
06/07/2005 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :* 1) ADDRESSING IS EXTREMELY IMPORTANT. 2) ADDRESS ON THE CURB, MAILBOX AND HOUSE MUST MATCH THE PERMIT ADDRESS. 3) ALL NEW WORK TO BE EXPOSED.