Permit: T05PL00439

Parcel: 118035850


Addresses:

1319 S COPIAS WY

Inspection Status: Denied

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
03/09/2005 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999* 1) SHALL PROVIDE BONDING TO GAS SYSTEM @ ELECTRICAL PANEL OR TO GROUNDED WATER WITH MIN #6 WIRE. 2) SHALL OBTAIN A WATER HTR PERMIT. 3) SHALL PROVIDE ( 3) SHEET METAL SCREWS PER JOINT @ WATER HTR FLU VENT CONNECTOR AND @ APPLIANCE COLLAR. 4) SHALL APPLY TAPER PRIMER AND 10 MIL TAPE @ METER GAS RISER & WRENCH MARKS. 5) SHALL PROVIDE REQUIRED TEST GAGE. 6) SHALL PROVIDE TWO HOLE STRAP ON ROOF.
03/09/2005 PLUMBING - FINAL Approved IVRS - Inspection :* 1) GAS PRESSURE TEST IS OK. 2) GAS SHUT OFF VALVES OK. 3) WATER HTR FLU VENT, T & P VALVE & DRAIN IS OK. 4) GAS PACK ON ROOF IS OK. 5) OK TO BACKFILL TRENCH.