Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - YARD WTR LINE/TEST
Permit Number - T05PL00110
Inspection Description - PLUMBING - YARD WTR LINE/TEST
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
11/17/2005 | PLUMBING - YARD WTR LINE/TEST | Approved | YARD WATER APPROVED BY B BENEDON. CONTRACTOR TO SHOW INSPECTOR FINAL CONNECTION TO BLDG | |
11/16/2005 | PLUMBING - YARD WTR LINE/TEST | Approved | IVRS - Inspection :*WATER PRESSURE TEST OK. 70 PSI ON GUAGE AT RPS | |
11/15/2005 | PLUMBING - YARD WTR LINE/TEST | Denied | IVRS - Inspection : See detailed listing on site.| 999* UNDERGROUND WATER DISTRIBUTION HAS A LEAK SOME WHERE. |
|
11/09/2005 | PLUMBING - YARD WTR LINE/TEST | Partial Approval | IVRS - Inspection :*SITE WATER SERVICE IS OK AS INITIALED ON PRIVATE UTILITY PLAN. NOTE: UTILITY CONTRACTOR SAID HE WAS TO PROVIDE AN AIR TEST @ A LATER TIME. COVER @ YOUR OWN RISK |
|
10/24/2005 | PLUMBING - YARD WTR LINE/TEST | Partial Approval | IVRS - Inspection :*SHALL SEE FINAL CONNECTION TO 4" MAIN AND BLDG SERVICE FOR 3/4" SUPPLY TO BLDG PRIMARY NORTH SHALL PROVIDE A AIR OR METER PRESSURE TEST. OK TO BACKFILL TRENCH. |
|
07/20/2005 | PLUMBING - YARD WTR LINE/TEST | Partial Approval | IVRS - Inspection :* 1) 4" PVC SITE WATER SERVICE IS OK FROM S.W. CORNER OF INTERMEDIATE EAST TO STAFF TESTING BLDG. CENTER AS NOTED ON PLAN 2) OK TO BACKFILL TRENCH |