Permit: T05PL00110

Parcel: 110034830

Inspection Status: Approved

Inspection History: PLUMBING - YARD WTR LINE/TEST

Permit Number - T05PL00110

Inspection Description - PLUMBING - YARD WTR LINE/TEST

Inspection Status - Approved

Date Description Inspector Results Comments
11/17/2005 PLUMBING - YARD WTR LINE/TEST Approved YARD WATER APPROVED BY B BENEDON. CONTRACTOR TO SHOW INSPECTOR FINAL CONNECTION TO BLDG
11/16/2005 PLUMBING - YARD WTR LINE/TEST Approved IVRS - Inspection :*WATER PRESSURE TEST OK. 70 PSI ON GUAGE AT RPS
11/15/2005 PLUMBING - YARD WTR LINE/TEST Denied IVRS - Inspection :
See detailed listing on site.| 999* UNDERGROUND WATER DISTRIBUTION HAS A LEAK SOME WHERE.
11/09/2005 PLUMBING - YARD WTR LINE/TEST Partial Approval IVRS - Inspection :*SITE WATER SERVICE IS OK AS INITIALED ON PRIVATE UTILITY PLAN.
NOTE: UTILITY CONTRACTOR SAID HE WAS TO PROVIDE AN AIR TEST @ A LATER TIME. COVER @ YOUR OWN RISK
10/24/2005 PLUMBING - YARD WTR LINE/TEST Partial Approval IVRS - Inspection :*SHALL SEE FINAL CONNECTION TO 4" MAIN AND BLDG SERVICE FOR 3/4" SUPPLY TO BLDG PRIMARY NORTH
SHALL PROVIDE A AIR OR METER PRESSURE TEST.
OK TO BACKFILL TRENCH.
07/20/2005 PLUMBING - YARD WTR LINE/TEST Partial Approval IVRS - Inspection :*
1) 4" PVC SITE WATER SERVICE IS OK FROM S.W. CORNER OF INTERMEDIATE EAST TO STAFF TESTING BLDG. CENTER AS NOTED ON PLAN
2) OK TO BACKFILL TRENCH