Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T05OT02811
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/17/2006 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
01/13/2006 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :*P-3 JANITOR TO BE DIRECTLY CONNECTED TO S.S AS THE PLAN SHOWS. WHERE IS THE VENT DOWN STREAM OF THE GREASE TRAP WHERE IS THE TRAP BEFORE THE GREASE TRAP AS SHOWN ON THE PLAN. ICE MAKER DRIAN MORE THAN FIVE FEET IN LENGTH. MUST BE DIRECTLY TRAPPED. INSTALL AT 1/4" PER FOOT. REMOVE COMP. FITTING REMOVE CAPPED TEE. ALL IN WASTE MUST HAVE MIN 1" AIR GAP. ??? WASTE TO BE APPROVED MATERIAL |
|
11/28/2005 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :*SPOKE W/BOB 11/25.05 REGARDING BOTH GOING OUT MONDAY. ADVISED CUSTOMER TO HAVE PLUMBER ON SITE FOR INSPECTION. BOB AGREED TO HAVE BOTH OF THEM THERE. | |
11/16/2005 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :*FINISH CONNECTING SODA FOUNTAIN EACH WATER SUPPLIED DEVICE IS TO HAVE ITS OWN BACKFLOW PROTECTION, AND ITS OWN DRAIN. ALL INDERECT WASTE PIPING TO HAVE AN AIRGAP BE OF APPROVED MATERIALS INSTALLED PER 94 UPC NO EXPNASION TANK ON WATER HEATER. MAY NOT INTERMINGLE MATERIAL TYPES OR GRADES. WHE?? GAS APPLIANCES TO HAVE CABLE RESTRAINT AND QUICK DISCONNECT. MAY NOT BE A COMPLETE LIST INSTALL FLOW CONTROL GREASE TRAP MAY NOT DUMP INTO THE FLOOR SINK |