Permit: T05ME00573

Parcel: 133180330


Addresses:

6901 E 2ND ST

Inspection Status: Denied

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
08/17/2005 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PROVIDE A MINIMUM 1/4" PER FT SLOPE ON FURNACE VENT CONNECTOR
2) FURNACE IS BLOCKING REMOVAL OF WATER HEATER
3) FITTERS CANNOT BE REMOVED
4) VENT IS BLOCKING ACCESS TO AIR CLEANER
5) GAS IS LEAKING INSIDE FURNACE ROOM POSSIBLY FROM OLD SHUT OFF VALVE
6) PROVIDE A HIGH COMBUSTION AIR OPENING