Inspection History Details
Inspection Status: Denied
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/17/2005 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PROVIDE A MINIMUM 1/4" PER FT SLOPE ON FURNACE VENT CONNECTOR 2) FURNACE IS BLOCKING REMOVAL OF WATER HEATER 3) FITTERS CANNOT BE REMOVED 4) VENT IS BLOCKING ACCESS TO AIR CLEANER 5) GAS IS LEAKING INSIDE FURNACE ROOM POSSIBLY FROM OLD SHUT OFF VALVE 6) PROVIDE A HIGH COMBUSTION AIR OPENING |