Inspection History Details
Inspection Status: Approved
Inspection History: INSP - FULL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/17/2006 | INSP - FULL | Approved | ||
| 10/27/2005 | INSP - FULL | Violation | 1). Fire alarm shall be repaired and then tested, and report shall be submitted to TFD. IFC 901.6 2). Sprinkler test and inspection report shall be submitted to TFD and all required repairs shall be submitted. IFC 901.6 3). Exit lights are out of service in the following area and shall be repaired. 2nd floor. IFC 1026.5 4). Door closures shall be repaired in the following areas; room 221, and Black room. IFC 703.2.2 5). Exhaust shall be cleaned, and (OR) proof of prior cleaning shall be shown. IFC 904.11.6.3, which states; 904.11.6.3 Cleaning. Hoods. Grease-removal devices, fans, ducts and other appurtenances shall be cleaned at intervals necessary to prevent the accumulation of grease. Cleanings shall be recorded, and records shall state the extent, time and date of cleaning. Such records shall be maintained on the premises. 6). All windows shall be repaired in courtyard. IFC 306 7). Remove mattress away from hot water heats. IFC 515 |