Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

10/27/2005

Applicant:

EPSILON EPSILON EDUCATIONAL FOUNDATION

Description:

inspection

Outstanding Inspections

Case Number: T05FR01694
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 1
End Date Description Inspector Results Comments
INSP - REINSPECTION None Not Inspected

Completed Inspections

Case Status: COMPLETE
Case Number: T05FR01694
Case Description: INSPECTION
Total Completed Inspections - 9
End Date Description Inspector Results Comments
10/27/2005 INSP - FULL EGRIFFIN Approved 1). Fire alarm shall be repaired and then tested, and report shall be submitted to TFD. IFC 901.6 2). Sprinkler test and inspection report shall be submitted to TFD and all required repairs shall be submitted. IFC 901.6 3). Exit lights are out of service in the following area and shall be repaired. 2nd floor. IFC 1026.5 4). Door closures shall be repaired in the following areas; room 221, and Black room. IFC 703.2.2 5). Exhaust shall be cleaned, and (OR) proof of prior cleaning shall be shown. IFC 904.11.6.3, which states; 904.11.6.3 Cleaning. Hoods. Grease-removal devices, fans, ducts and other appurtenances shall be cleaned at intervals necessary to prevent the accumulation of grease. Cleanings shall be recorded, and records shall state the extent, time and date of cleaning. Such records shall be maintained on the premises. 6). All windows shall be repaired in courtyard. IFC 306 7). Remove mattress away from hot water heats. IFC 515
11/22/2005 VIOL - PRECAUTION AGAINST FIRE EGRIFFIN Approved Remove mattress away from hot water heaters. IFC 515
11/22/2005 VIOL - PRECAUTION AGAINST FIRE EGRIFFIN Approved All windows shall be repaired in courtyard. IFC 306
11/22/2005 VIOL - FIRE RESIST.RATED CONST EGRIFFIN Approved Door closures shall be repaired in the following areas; room 221, and Black room. IFC 703.2.2
11/22/2005 VIOL - MEANS OF EGRESS EGRIFFIN Approved Exit lights are out of service in the following area and shall be repaired. 2nd floor. IFC 1026.5
11/22/2005 VIOL - FIRE PROTECTION SYSTEMS EGRIFFIN Approved Exhaust shall be cleaned, and (OR) proof of prior cleaning shall be shown. IFC 904.11.6.3, which states; 904.11.6.3 Cleaning. Hoods. Grease-removal devices, fans, ducts and other appurtenances shall be cleaned at intervals necessary to prevent the accumulation of grease. Cleanings shall be recorded, and records shall state the extent, time and date of cleaning. Such records shall be maintained on the premises.
11/22/2005 VIOL - FIRE PROTECTION SYSTEMS EGRIFFIN Approved Sprinkler test and inspection report shall be submitted to TFD and all required repairs shall be submitted. IFC 901.6
11/22/2005 VIOL - FIRE PROTECTION SYSTEMS EGRIFFIN Approved 1). Fire alarm shall be repaired and then tested, and report shall be submitted to TFD. IFC 901.6
01/17/2006 COMPLIANCE EGRIFFIN Approved