Case: T05FR01405

Parcel: 10922021E

Inspection Status: Continued

Inspection History: VIOL - MEANS OF EGRESS

Date Description Inspector Results Comments
01/12/2007 VIOL - MEANS OF EGRESS Continued
09/14/2005 VIOL - MEANS OF EGRESS Violation TFC 2003 1003.6 Means of egress continuity.
The path of egress travel along a means of egress shall not be interrupted by any building element.
1. The emergency exits from the two bedrooms that exit into the pool area have no exit pathway to the outside.
Cearte an exit pathway to the exit gate on the east side of the pool area, that both bedrooms can use as a exit pathway and place a thumb type lock if needed.
09/14/2005 VIOL - MEANS OF EGRESS Violation TFC 2003 1026.5 Illumination emergency power.
The power supply for means of egress illumination shall normally be provided by the premises’ electrical supply. In the event of power supply failure, illumination shall be automatically provided from an
emergency system for the following occupancies where such occupancies require two or more means of egress:
1. Emergency lighting for exit is required on all exsisting group home building