Case Number: T05FR01405
Case Status: REFERRED
Case Description: INSPECTION
Total Outstanding Inspections - 4
End Date Description Inspector Results Comments
09/14/2005 VIOL - ADMINISTRATION SHIGGINB Violation TFC 2003 102.3 Change of use or occupancy. 1. No certificate of occupancy Refered to DSD
09/14/2005 VIOL - FIRE PROTECTION SYSTEMS SHIGGINB Violation TFC 2003 907.3.1.8 Group R-4. A fire alarm system shall be installed in existing Group R-4 residential care/assisted living facilities. Exceptions: 1. Where there are interconnected smoke alarms\ meeting the requirements of Section 907.2.10 and there is at least one manual fire alarm box per floor arranged to sound continuously the smoke alarms. 2. Other manually activated, continuously sounding alarms approved by the fire code official.
09/14/2005 VIOL - MEANS OF EGRESS SHIGGINB Violation TFC 2003 1003.6 Means of egress continuity. The path of egress travel along a means of egress shall not be interrupted by any building element. 1. The emergency exits from the two bedrooms that exit into the pool area have no exit pathway to the outside. Cearte an exit pathway to the exit gate on the east side of the pool area, that both bedrooms can use as a exit pathway and place a thumb type lock if needed.
09/14/2005 VIOL - MEANS OF EGRESS SHIGGINB Violation TFC 2003 1026.5 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premises’ electrical supply. In the event of power supply failure, illumination shall be automatically provided from an emergency system for the following occupancies where such occupancies require two or more means of egress: 1. Emergency lighting for exit is required on all exsisting group home building

Completed Inspections

Case Status: REFERRED
Case Number: T05FR01405
Case Description: INSPECTION
Total Completed Inspections - 4
End Date Description Inspector Results Comments
09/14/2005 VIOL - PRECAUTION AGAINST FIRE SHIGGINB Approved TFC 2003 307.3.2 Recreational fires. and 307.4 Attendance. See handout Recreational fires. 1. Also a hose bib must be places near the fire pit so a 50' garden hose can reach 15' to the other side of fire pit. This garden hose must be charged at time when fire pit is in use. 2. Create a safety checklist of pre-setup and post break-down of fire pit with name of attendant. Save for 3 yrs.
09/14/2005 VIOL - BUILDING SVCS & SYSTEMS SHIGGINB Approved TFC 2003 605.1 Abatement of electrical hazards. Identified electrical hazards shall be abated. 1. Place all electrical wires on the outside of building in conduit.
09/14/2005 VIOL - FIRE SERVICE FEATURES SHIGGINB Approved TFC 2003 505.1 Address numbers. New and existing buildings shall have approved address numbers, 1. Place address at street and place on building, 3" numbers w/ contrasting background
01/12/2007 COMPL - INITIAL INSPECTION SHIGGINB Approved