Case: T05FR01141

Parcel: 132160390


Addresses:

1309 E BENSON HY

Inspection Status: No Violation

Inspection History: VIOL - FIRE PROTECTION SYSTEMS

Date Description Inspector Results Comments
08/29/2005 VIOL - FIRE PROTECTION SYSTEMS No Violation Owner has moved woodworking process outside of structure, no longer necessary to sprinkler. Owner has been warned of moving operation inside without proper fire protection, citation would be issued if this happened.
07/21/2005 VIOL - FIRE PROTECTION SYSTEMS Violation TFC Fire extinguishers shall be serviced annually and have the current tag attached.
07/21/2005 VIOL - FIRE PROTECTION SYSTEMS Violation TFC 906.7- Fire extinguishers shall be mounted on hangers or brackets and securely anchored.
07/21/2005 VIOL - FIRE PROTECTION SYSTEMS Violation TFC 903.2.3.1- Woodworking Operations. An automatic sprinkler system shall be provided throughout all Group F-1 occupancy fire areas that contain woodworking operations in excess of 2500 square feet in area which generate finely divided combustible waste or which use finely divided combustible materials.