Case: T05FR01141
Case Details
Entered Date:
07/21/2005
Applicant:
KUNDERT GENELLE M
Description:
Inspection
Outstanding Inspections
Case Number: T05FR01141
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 11
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| INSP - FULL | None | Not Inspected | ||
| 07/21/2005 | VIOL - ADMINISTRATION | JLANGEJA | Violation | TFC 102.6- No building or structure shall be used or occupied...until the building official has issued a Certificate of Occupancy. It shall be posted in a conspicuous location. ***Applied on 1-03-05 |
| 07/21/2005 | VIOL - PRECAUTION AGAINST FIRE | JLANGEJA | Violation | TFC 310.3- A "NO SMOKING" sign shall be posted on the East side of the building. |
| 07/21/2005 | VIOL - EMERGENCY PLAN/PREPARE | JLANGEJA | Violation | TFC 407.2- Material Safety Data Sheets for all hazardous materials shall be readily available on the premises. |
| 07/21/2005 | VIOL - BUILDING SVCS & SYSTEMS | JLANGEJA | Violation | TFC 605.3- A working space of 30" in width, 36" in depth and 78" in height shall be provided in front of electrical service equipment. |
| 07/21/2005 | VIOL - BUILDING SVCS & SYSTEMS | JLANGEJA | Violation | TFC 605.5- Extension cords shall not be a substitute for permanent wiring. 1. office area 2. outside to washing machine |
| 07/21/2005 | VIOL - BUILDING SVCS & SYSTEMS | JLANGEJA | Violation | TFC 605.6- Open junction boxes and open wiring splices shall be prohibited. 1. open j-box on S wall 2. open j-box on N wall |
| 07/21/2005 | VIOL - MEANS OF EGRESS | JLANGEJA | Violation | TFC 1011.5.3-Exit signs shall be illuminated at all times. |
| 07/21/2005 | VIOL - MEANS OF EGRESS | JLANGEJA | Violation | TFC 1011.1- Exit doors shall be marked with an approved exit sign readily visible from any direction. (E wall) |
| 07/21/2005 | VIOL - LUMBER YARD & WOOD FAC. | JLANGEJA | Violation | TFC 1903.2- Equipment or machinery located inside buildings which generates or emits combustible dust shall be provided with an approved dust collection and exhaust system. |
| 07/21/2005 | VIOL - LUMBER YARD & WOOD FAC. | JLANGEJA | Violation | TFC 1903.3.1- Provisions shall be made for a systematic and thorough cleaning of the entire plant to prevent accumulation of combustible dust. |
Completed Inspections
Case Status: COMPLETE
Case Number: T05FR01141
Case Description: INSPECTION
Total Completed Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/29/2005 | VIOL - FIRE PROTECTION SYSTEMS | JLANGEJA | Approved | Owner has moved woodworking process outside of structure, no longer necessary to sprinkler. Owner has been warned of moving operation inside without proper fire protection, citation would be issued if this happened. |