End Date Description Inspector Results Comments
INSP - FULL None Not Inspected
07/21/2005 VIOL - ADMINISTRATION JLANGEJA Violation TFC 102.6- No building or structure shall be used or occupied...until the building official has issued a Certificate of Occupancy. It shall be posted in a conspicuous location. ***Applied on 1-03-05
07/21/2005 VIOL - PRECAUTION AGAINST FIRE JLANGEJA Violation TFC 310.3- A "NO SMOKING" sign shall be posted on the East side of the building.
07/21/2005 VIOL - EMERGENCY PLAN/PREPARE JLANGEJA Violation TFC 407.2- Material Safety Data Sheets for all hazardous materials shall be readily available on the premises.
07/21/2005 VIOL - BUILDING SVCS & SYSTEMS JLANGEJA Violation TFC 605.3- A working space of 30" in width, 36" in depth and 78" in height shall be provided in front of electrical service equipment.
07/21/2005 VIOL - BUILDING SVCS & SYSTEMS JLANGEJA Violation TFC 605.5- Extension cords shall not be a substitute for permanent wiring. 1. office area 2. outside to washing machine
07/21/2005 VIOL - BUILDING SVCS & SYSTEMS JLANGEJA Violation TFC 605.6- Open junction boxes and open wiring splices shall be prohibited. 1. open j-box on S wall 2. open j-box on N wall
07/21/2005 VIOL - MEANS OF EGRESS JLANGEJA Violation TFC 1011.5.3-Exit signs shall be illuminated at all times.
07/21/2005 VIOL - MEANS OF EGRESS JLANGEJA Violation TFC 1011.1- Exit doors shall be marked with an approved exit sign readily visible from any direction. (E wall)
07/21/2005 VIOL - LUMBER YARD & WOOD FAC. JLANGEJA Violation TFC 1903.2- Equipment or machinery located inside buildings which generates or emits combustible dust shall be provided with an approved dust collection and exhaust system.
07/21/2005 VIOL - LUMBER YARD & WOOD FAC. JLANGEJA Violation TFC 1903.3.1- Provisions shall be made for a systematic and thorough cleaning of the entire plant to prevent accumulation of combustible dust.

Completed Inspections

Case Status: COMPLETE
Case Number: T05FR01141
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
08/29/2005 VIOL - FIRE PROTECTION SYSTEMS JLANGEJA Approved Owner has moved woodworking process outside of structure, no longer necessary to sprinkler. Owner has been warned of moving operation inside without proper fire protection, citation would be issued if this happened.