Case: T05FR00925

Parcel: 11619131A


Addresses:

707 W CONGRESS ST


Inspection Status: Correction Required

Inspection History: VIOL - FLAMMABLE FINISHES

Case Number - T05FR00925

Inspection Description - VIOL - FLAMMABLE FINISHES

Inspection Status - Correction Required

Date Description Inspector Results Comments
06/21/2005 VIOL - FLAMMABLE FINISHES Correction Required 1504.1 Spray finishing operations are not being conducted within a spray room, spray booth, or limited spraying space.
06/21/2005 VIOL - FLAMMABLE FINISHES Correction Required 1504.1.4.2 Spray finishing operations conducted in a limited spraying space shall not be of a continuous nature.
06/21/2005 VIOL - FLAMMABLE FINISHES Correction Required 1504.1.4.3 Ventilation system in spray area does not meet the requirements for handling flammable vapors.
06/21/2005 VIOL - FLAMMABLE FINISHES Correction Required 1504.1.4.1 The aggregate surface to be sprayed shall not be over 9 square feet in a limited spraying space
06/21/2005 VIOL - FLAMMABLE FINISHES Correction Required 1504.1.4.4 Electrical wiring within 10 feet of the floor and 20 feet horizontally shall be Class 1, Division 2.
06/21/2005 VIOL - FLAMMABLE FINISHES Correction Required 1504.6.4 Area shall have a 4A-40B extinguisher within 30 feet.