Inspection History Details
Inspection Status: Correction Required
Inspection History: VIOL - FLAMMABLE FINISHES
Case Number - T05FR00925
Inspection Description - VIOL - FLAMMABLE FINISHES
Inspection Status - Correction Required
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/21/2005 | VIOL - FLAMMABLE FINISHES | Correction Required | 1504.1 Spray finishing operations are not being conducted within a spray room, spray booth, or limited spraying space. | |
06/21/2005 | VIOL - FLAMMABLE FINISHES | Correction Required | 1504.1.4.2 Spray finishing operations conducted in a limited spraying space shall not be of a continuous nature. | |
06/21/2005 | VIOL - FLAMMABLE FINISHES | Correction Required | 1504.1.4.3 Ventilation system in spray area does not meet the requirements for handling flammable vapors. | |
06/21/2005 | VIOL - FLAMMABLE FINISHES | Correction Required | 1504.1.4.1 The aggregate surface to be sprayed shall not be over 9 square feet in a limited spraying space | |
06/21/2005 | VIOL - FLAMMABLE FINISHES | Correction Required | 1504.1.4.4 Electrical wiring within 10 feet of the floor and 20 feet horizontally shall be Class 1, Division 2. | |
06/21/2005 | VIOL - FLAMMABLE FINISHES | Correction Required | 1504.6.4 Area shall have a 4A-40B extinguisher within 30 feet. |