Inspection Status: Correction Required
Inspection History: VIOL - FLAMMABLE FINISHES
| Date |
Description |
Inspector |
Results |
Comments |
| 06/21/2005 |
VIOL - FLAMMABLE FINISHES |
|
Correction Required |
1504.1 Spray finishing operations are not being conducted within a spray room, spray booth, or limited spraying space. |
| 06/21/2005 |
VIOL - FLAMMABLE FINISHES |
|
Correction Required |
1504.1.4.2 Spray finishing operations conducted in a limited spraying space shall not be of a continuous nature. |
| 06/21/2005 |
VIOL - FLAMMABLE FINISHES |
|
Correction Required |
1504.1.4.3 Ventilation system in spray area does not meet the requirements for handling flammable vapors. |
| 06/21/2005 |
VIOL - FLAMMABLE FINISHES |
|
Correction Required |
1504.1.4.1 The aggregate surface to be sprayed shall not be over 9 square feet in a limited spraying space |
| 06/21/2005 |
VIOL - FLAMMABLE FINISHES |
|
Correction Required |
1504.1.4.4 Electrical wiring within 10 feet of the floor and 20 feet horizontally shall be Class 1, Division 2. |
| 06/21/2005 |
VIOL - FLAMMABLE FINISHES |
|
Correction Required |
1504.6.4 Area shall have a 4A-40B extinguisher within 30 feet. |