Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.

Case: T05FR00925

Parcel: 11619131A


Addresses:

707 W CONGRESS ST

Inspection Status: Correction Required

Inspection History: VIOL - FLAMMABLE FINISHES

Date Description Inspector Results Comments
06/21/2005 VIOL - FLAMMABLE FINISHES Correction Required 1504.1 Spray finishing operations are not being conducted within a spray room, spray booth, or limited spraying space.
06/21/2005 VIOL - FLAMMABLE FINISHES Correction Required 1504.1.4.2 Spray finishing operations conducted in a limited spraying space shall not be of a continuous nature.
06/21/2005 VIOL - FLAMMABLE FINISHES Correction Required 1504.1.4.3 Ventilation system in spray area does not meet the requirements for handling flammable vapors.
06/21/2005 VIOL - FLAMMABLE FINISHES Correction Required 1504.1.4.1 The aggregate surface to be sprayed shall not be over 9 square feet in a limited spraying space
06/21/2005 VIOL - FLAMMABLE FINISHES Correction Required 1504.1.4.4 Electrical wiring within 10 feet of the floor and 20 feet horizontally shall be Class 1, Division 2.
06/21/2005 VIOL - FLAMMABLE FINISHES Correction Required 1504.6.4 Area shall have a 4A-40B extinguisher within 30 feet.