Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

06/21/2005

Applicant:

BECK RUDY C

Description:

Full Inspection

Outstanding Inspections

Case Number: T05FR00925
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 7
End Date Description Inspector Results Comments
INSP - FULL None Not Inspected
06/21/2005 VIOL - FLAMMABLE FINISHES TKNAPP Correction Required 1504.1 Spray finishing operations are not being conducted within a spray room, spray booth, or limited spraying space.
06/21/2005 VIOL - FLAMMABLE FINISHES TKNAPP Correction Required 1504.1.4.1 The aggregate surface to be sprayed shall not be over 9 square feet in a limited spraying space
06/21/2005 VIOL - FLAMMABLE FINISHES TKNAPP Correction Required 1504.1.4.2 Spray finishing operations conducted in a limited spraying space shall not be of a continuous nature.
06/21/2005 VIOL - FLAMMABLE FINISHES TKNAPP Correction Required 1504.1.4.3 Ventilation system in spray area does not meet the requirements for handling flammable vapors.
06/21/2005 VIOL - FLAMMABLE FINISHES TKNAPP Correction Required 1504.1.4.4 Electrical wiring within 10 feet of the floor and 20 feet horizontally shall be Class 1, Division 2.
06/21/2005 VIOL - FLAMMABLE FINISHES TKNAPP Correction Required 1504.6.4 Area shall have a 4A-40B extinguisher within 30 feet.