Case: T05FR00813

Parcel: 11901067G


Addresses:

3355 S 6TH AV


Inspection Status: Approved

Inspection History: VIOL - MEANS OF EGRESS

Case Number - T05FR00813

Inspection Description - VIOL - MEANS OF EGRESS

Inspection Status - Approved

Date Description Inspector Results Comments
06/20/2005 VIOL - MEANS OF EGRESS Approved
06/06/2005 VIOL - MEANS OF EGRESS Violation 1). Currently on rear exit, there is an additional locking device, in addition to panic hardware (push bar) on rear exit.

Tucson Fire Code states:

Section 1027.6 Panic hardware. Where panic and fire exit hardware is installed, whether required or not, panic or fire exit hardware shall be the only locking device on the door except where otherwise permitted in this code.

The additional locking device shall be removed.