Inspection History Details
Inspection Status: Violation
Inspection History: VIOL - BUILDING SVCS & SYSTEMS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/26/2005 | VIOL - BUILDING SVCS & SYSTEMS | Violation | TFC 605.6- Open junction boxes and open wiring splices shall be prohibited. Approved covers shall be provided. 1. front office needs switch plate. 2. H2O heater room junction box covered. 3. storage room needs switch cover. 4. office upstairs needs switch cover.- |
|
| 05/26/2005 | VIOL - BUILDING SVCS & SYSTEMS | Violation | TFC Identified electrical hazards shall be abated.The receptacle above the sink shall have GFI protection. | |
| 05/26/2005 | VIOL - BUILDING SVCS & SYSTEMS | Violation | TFC 605.3- A working space of 30" x 36" x 78" shall be provided in front of electrical service equipment. |