Description:
Inspection
Outstanding Inspections
Case Number: T05FR00780
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 9
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| INSP - FULL | None | Not Inspected | ||
| 05/26/2005 | VIOL - ADMINISTRATION | JLANGEJA | Violation | TBC 110.1- No building or structure shall be used or occupied...until the building official has issued a Certificate of Occupancy. One may be obtained at Development Services @ 201 N. Stone. |
| 05/26/2005 | VIOL - PRECAUTION AGAINST FIRE | JLANGEJA | Violation | TFC 315.2.1- Storage of combustibles shall be maintained a minimum of 2 feet below the ceiling. |
| 05/26/2005 | VIOL - BUILDING SVCS & SYSTEMS | JLANGEJA | Violation | TFC 605.3- A working space of 30" x 36" x 78" shall be provided in front of electrical service equipment. |
| 05/26/2005 | VIOL - BUILDING SVCS & SYSTEMS | JLANGEJA | Violation | TFC 605.6- Open junction boxes and open wiring splices shall be prohibited. Approved covers shall be provided. 1. front office needs switch plate. 2. H2O heater room junction box covered. 3. storage room needs switch cover. 4. office upstairs needs switch cover.- |
| 05/26/2005 | VIOL - BUILDING SVCS & SYSTEMS | JLANGEJA | Violation | TFC Identified electrical hazards shall be abated.The receptacle above the sink shall have GFI protection. |
| 05/26/2005 | VIOL - FIRE RESIST.RATED CONST | JLANGEJA | Violation | TFC703.1- Fire resistance-rated construction shall be maintained. Holes shall be repaired in H2O heater room. |
| 05/26/2005 | VIOL - FIRE PROTECTION SYSTEMS | JLANGEJA | Violation | TFC 906.3- Fire extinguishers shall be required in storage occupancies. A minimum size of 2A is required. The maximum travel distance shall be 75 feet. |
| 05/26/2005 | VIOL - MEANS OF EGRESS | JLANGEJA | Violation | TFC 1009.11- Stairways shall have handrails on both sides. |