Inspection History Details
Inspection Status: Violation
Inspection History: VIOL - BUILDING SVCS & SYSTEMS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/17/2005 | VIOL - BUILDING SVCS & SYSTEMS | Violation | TFC 605.5- Extension cords shall not be a substitute for permanent wiring. (several in showroom) | |
| 05/17/2005 | VIOL - BUILDING SVCS & SYSTEMS | Violation | TFC 605.4- Multiplug adapters shall be prohibited. (showroom) | |
| 05/17/2005 | VIOL - BUILDING SVCS & SYSTEMS | Violation | TFC 605.6- Open junction boxes and open wiring splices shall be prohibited. 1. cover on junction box 2. electrical panel needs blanks |
|
| 05/17/2005 | VIOL - BUILDING SVCS & SYSTEMS | Violation | TFC 605.3- A working space of 30" in width, 36" in depth and 78" in height shall be provided in front of electrical service equipment. |