Case: T05FR00690

Parcel: 124182360


Addresses:

1028 S CURTIS AV

Inspection Status: Violation

Inspection History: VIOL - BUILDING SVCS & SYSTEMS

Date Description Inspector Results Comments
05/17/2005 VIOL - BUILDING SVCS & SYSTEMS Violation TFC 605.5- Extension cords shall not be a substitute for permanent wiring. (several in showroom)
05/17/2005 VIOL - BUILDING SVCS & SYSTEMS Violation TFC 605.4- Multiplug adapters shall be prohibited. (showroom)
05/17/2005 VIOL - BUILDING SVCS & SYSTEMS Violation TFC 605.6- Open junction boxes and open wiring splices shall be prohibited.
1. cover on junction box
2. electrical panel needs blanks
05/17/2005 VIOL - BUILDING SVCS & SYSTEMS Violation TFC 605.3- A working space of 30" in width, 36" in depth and 78" in height shall be provided in front of electrical service equipment.