Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

05/17/2005

Applicant:

JOHNSON FRANK L & LUCILE JT/RS

Description:

Inspection

Outstanding Inspections

Case Number: T05FR00690
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 9
End Date Description Inspector Results Comments
INSP - FULL None Not Inspected
05/17/2005 VIOL - ADMINISTRATION JLANGEJA Violation TBC 110.1- No building or structure shall be used or occupied...until the building official has issued a Certificate of Occupancy.
05/17/2005 VIOL - BUILDING SVCS & SYSTEMS JLANGEJA Violation TFC 605.3- A working space of 30" in width, 36" in depth and 78" in height shall be provided in front of electrical service equipment.
05/17/2005 VIOL - BUILDING SVCS & SYSTEMS JLANGEJA Violation TFC 605.4- Multiplug adapters shall be prohibited. (showroom)
05/17/2005 VIOL - BUILDING SVCS & SYSTEMS JLANGEJA Violation TFC 605.5- Extension cords shall not be a substitute for permanent wiring. (several in showroom)
05/17/2005 VIOL - BUILDING SVCS & SYSTEMS JLANGEJA Violation TFC 605.6- Open junction boxes and open wiring splices shall be prohibited. 1. cover on junction box 2. electrical panel needs blanks
05/17/2005 VIOL - FIRE PROTECTION SYSTEMS JLANGEJA Violation TFC 901.6- Fire extinguishers shall be serviced annually.
05/17/2005 VIOL - MEANS OF EGRESS JLANGEJA Violation TFC 1003.6- The path of egress travel shall not be interrupted.
05/17/2005 VIOL - FLAMMABLE FINISHES JLANGEJA Violation TFC 1503.2.6- "NO SMOKING" sign shall be conspicuously posted and legible. (spray booth)