Case Number: T05FR00690
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 9
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| INSP - FULL | None | Not Inspected | ||
| 05/17/2005 | VIOL - ADMINISTRATION | JLANGEJA | Violation | TBC 110.1- No building or structure shall be used or occupied...until the building official has issued a Certificate of Occupancy. |
| 05/17/2005 | VIOL - BUILDING SVCS & SYSTEMS | JLANGEJA | Violation | TFC 605.3- A working space of 30" in width, 36" in depth and 78" in height shall be provided in front of electrical service equipment. |
| 05/17/2005 | VIOL - BUILDING SVCS & SYSTEMS | JLANGEJA | Violation | TFC 605.4- Multiplug adapters shall be prohibited. (showroom) |
| 05/17/2005 | VIOL - BUILDING SVCS & SYSTEMS | JLANGEJA | Violation | TFC 605.5- Extension cords shall not be a substitute for permanent wiring. (several in showroom) |
| 05/17/2005 | VIOL - BUILDING SVCS & SYSTEMS | JLANGEJA | Violation | TFC 605.6- Open junction boxes and open wiring splices shall be prohibited. 1. cover on junction box 2. electrical panel needs blanks |
| 05/17/2005 | VIOL - FIRE PROTECTION SYSTEMS | JLANGEJA | Violation | TFC 901.6- Fire extinguishers shall be serviced annually. |
| 05/17/2005 | VIOL - MEANS OF EGRESS | JLANGEJA | Violation | TFC 1003.6- The path of egress travel shall not be interrupted. |
| 05/17/2005 | VIOL - FLAMMABLE FINISHES | JLANGEJA | Violation | TFC 1503.2.6- "NO SMOKING" sign shall be conspicuously posted and legible. (spray booth) |