Case: T05FR00666

Parcel: 124182540


Addresses:

1230 E 21ST ST

Inspection Status: Violation

Inspection History: VIOL - BUILDING SVCS & SYSTEMS

Date Description Inspector Results Comments
05/12/2005 VIOL - BUILDING SVCS & SYSTEMS Violation TFC 605.3- A working space of not less than 30" x 36" x 78" shall be provided in front of electrical service equipment.
05/12/2005 VIOL - BUILDING SVCS & SYSTEMS Violation TFC 605.1- Identified electrical hazards shall be abated.
1. open wiring splices to power strip on work bench
2. romex wire shall be protected below ceiling