Case: T05FR00666
Case Details
Entered Date:
05/12/2005
Applicant:
POWERS WILLIAM R III & BARBARA JEAN 1/2
Description:
Inspection
Outstanding Inspections
Case Number: T05FR00666
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 7
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| INSP - FULL | None | Not Inspected | ||
| 05/12/2005 | VIOL - ADMINISTRATION | JLANGEJA | Violation | TBC 110.1- No building or structure shall be used or occupied...until the building official has issued a Certificate of Occupancy. |
| 05/12/2005 | VIOL - PRECAUTION AGAINST FIRE | JLANGEJA | Violation | TFC 315.2.1- Storage shall be maintained a minimum of 2' below ceiling in a non-sprinklered building. |
| 05/12/2005 | VIOL - BUILDING SVCS & SYSTEMS | JLANGEJA | Violation | TFC 605.1- Identified electrical hazards shall be abated. 1. open wiring splices to power strip on work bench 2. romex wire shall be protected below ceiling |
| 05/12/2005 | VIOL - BUILDING SVCS & SYSTEMS | JLANGEJA | Violation | TFC 605.3- A working space of not less than 30" x 36" x 78" shall be provided in front of electrical service equipment. |
| 05/12/2005 | VIOL - FIRE PROTECTION SYSTEMS | JLANGEJA | Violation | TFC 901.6- Fire extinguishers shall be serviced annually. |
| 05/12/2005 | VIOL - FIRE PROTECTION SYSTEMS | JLANGEJA | Violation | TFC 906.7- Fire extinguishers shall be installed on their hanger or bracket and anchored securely. |