Inspection Status: Correction Required
Inspection History: INSP - NIGHT
| Date |
Description |
Inspector |
Results |
Comments |
| 05/11/2005 |
INSP - NIGHT |
|
Correction Required |
TFC 605.5 Electrical J-box cover plates missing check throughout business.TFC 906.5 Wrong size extinuguishers in business need 2A, 10BC extinguishers.TFC 3404.3 wood shop need housekeeping, saw dust need to remove daily.TFC 605.5 Elecrtical panel blocked need to be able to close door.also storage next to panel need to remove.fill in the open space with blanks.TFC 906.1 shall sprinkler the spray booth and over 2500 sq. ft. wood shop also needs the automatic sprinkler system.TFC 105.2 Cof O needed. TFC 407.2 MSDS sheets. TFC 3404.3.4.4 shall have a flammable liquid cabinet over 10 gallons of paints. |