Case Details

Status:

FIELD

Type:

INSPECTION
Address:

Entered Date:

05/11/2005

Applicant:

SCHMITZ RAYMOND R TR

Description:

full inspection

Outstanding Inspections

Case Number: T05FR00659
Case Status: FIELD
Case Description: INSPECTION
Total Outstanding Inspections - 8
End Date Description Inspector Results Comments
INSP - FULL None Not Inspected
VIOL - ADMINISTRATION None Not Inspected
VIOL - EMERGENCY PLAN/PREPARE None Not Inspected
VIOL - BUILDING SVCS & SYSTEMS None Not Inspected
VIOL - FIRE PROTECTION SYSTEMS None Not Inspected
VIOL - COMBUSTIBLE FIBERS None Not Inspected
VIOL - FLAMMABLE LIQUIDS None Not Inspected
05/11/2005 INSP - NIGHT FCONTRER Correction Required TFC 605.5 Electrical J-box cover plates missing check throughout business.TFC 906.5 Wrong size extinuguishers in business need 2A, 10BC extinguishers.TFC 3404.3 wood shop need housekeeping, saw dust need to remove daily.TFC 605.5 Elecrtical panel blocked need to be able to close door.also storage next to panel need to remove.fill in the open space with blanks.TFC 906.1 shall sprinkler the spray booth and over 2500 sq. ft. wood shop also needs the automatic sprinkler system.TFC 105.2 Cof O needed. TFC 407.2 MSDS sheets. TFC 3404.3.4.4 shall have a flammable liquid cabinet over 10 gallons of paints.