Inspection Status: Violation
Inspection History: VIOL - BUILDING SVCS & SYSTEMS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/04/2005 | VIOL - BUILDING SVCS & SYSTEMS | Violation | TFC 605.6- Open junction boxes shall be prohibited. | |
| 05/04/2005 | VIOL - BUILDING SVCS & SYSTEMS | Violation | TFC 605.3- A working space of not less than 30' in width, 36" in depth and 78" in height shall be provided in front of electrical service equipment. | |
| 05/04/2005 | VIOL - BUILDING SVCS & SYSTEMS | Violation | TFC 605.5- Extension cords shall not be a substitute for permanent wiring. (to evap. cooler) | |
| 05/04/2005 | VIOL - BUILDING SVCS & SYSTEMS | Violation | TFC 605.1- Identified electrical hazards shall be abated. 1. light fixture in sign room 2. light fixtures in hot work area 3. (water fountain) receptacle needs GFI |