Case: T05FR00604
Case Details
Entered Date:
05/04/2005
Applicant:
TKS 22ND STREET LLC
Description:
Inspection
Outstanding Inspections
Case Number: T05FR00604
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 15
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| INSP - FULL | None | Not Inspected | ||
| 05/04/2005 | VIOL - ADMINISTRATION | JLANGEJA | Violation | TBC 110.1- A C of O is required for this address. No building or structure shall be used or occupied...until the building official has issued a Certificate of Occupancy. |
| 05/04/2005 | VIOL - ADMINISTRATION | JLANGEJA | Violation | TFC 105.6.42- An operational permit is required to conduct a spraying or dipping operation utilizing flammable or combustible liquids or the application of combustible powders regulated by Chapter 15 of the IFC. We left Tim (owner) with a copy of Chapter 15. |
| 05/04/2005 | VIOL - ADMINISTRATION | JLANGEJA | Violation | TFC 110.1.1- Unsafe conditions: non-compliant spray booth. |
| 05/04/2005 | VIOL - ADMINISTRATION | JLANGEJA | Violation | TFC 111.2- Stop Work Order. Upon issuance of a stop work order, the cited work shall cease immediately. See Chapter 15, Flammable Finishes hand out. |
| 05/04/2005 | VIOL - BUILDING SVCS & SYSTEMS | JLANGEJA | Violation | TFC 605.1- Identified electrical hazards shall be abated. 1. light fixture in sign room 2. light fixtures in hot work area 3. (water fountain) receptacle needs GFI |
| 05/04/2005 | VIOL - BUILDING SVCS & SYSTEMS | JLANGEJA | Violation | TFC 605.3- A working space of not less than 30' in width, 36" in depth and 78" in height shall be provided in front of electrical service equipment. |
| 05/04/2005 | VIOL - BUILDING SVCS & SYSTEMS | JLANGEJA | Violation | TFC 605.5- Extension cords shall not be a substitute for permanent wiring. (to evap. cooler) |
| 05/04/2005 | VIOL - BUILDING SVCS & SYSTEMS | JLANGEJA | Violation | TFC 605.6- Open junction boxes shall be prohibited. |
| 05/04/2005 | VIOL - FIRE PROTECTION SYSTEMS | JLANGEJA | Violation | TFC 901.6- Fire extinguishers shall be serviced annually and anchored securely. |
| 05/04/2005 | VIOL - WELDING & OTHER HOT WRK | JLANGEJA | Violation | TFC 2606.4- An emergency disconnect switch or circuit breaker shall be installed in accordance with the ICC Electrical Code. It shall be marked "EMERGENCY DISCONNECT" and shall be visible from the equipment. |
| 05/04/2005 | VIOL - WELDING & OTHER HOT WRK | JLANGEJA | Violation | TFC Partitions segregating hot work areas from other areas of the building shall be non-combustible. Partitions shall prevent the passage of sparks, slag and heat from hot work area. |
| 05/04/2005 | VIOL - COMPRESSED GASES | JLANGEJA | Violation | TFC 3003.3- Compressed gas cylinders shall be secured to prevent accidental dislodgement. 1. sign shop 2. welding area |
| 05/04/2005 | VIOL - FLAMMABLE LIQUIDS | JLANGEJA | Violation | Flammable and combustible liquids-3404.3.2.1 Design and construction of storage cabinets. Design and construction of liquid storage cabinets shall be in accordance with this section. 3404.3.2.1.1 Materials. Cabinets shall be listed in accordance with UL 1275, or constructed of approved wood or metal in accordance with the following: 1. Unlisted metal cabinets shall be constructed of steel having a thickness of not less than 0.044 inch (1.12mm)(18 gage). The cabinet, including the door, shall be double walled with 1.5-inch (38 mm) airspace between the walls. Joints shall be riveted or welded and shall be tight fitting. 2. Unlisted wooden cabinets, including doors, shall be constructed of not less than 1-inch (25 mm) exterior grade plywood. Joints shall be rabbeted and shall be fastened in two directions with wood screws. Door hinges shall be of steel or brass. Cabinets shall be painted with an intumescent- type paint. 3404.3.2.1.2 Labeling. Cabinets shall be provided with a conspicuous label in red letters on contrasting background which reads: FLAMMABLE—KEEP FIRE AWAY. 3404.3.2.1.3 Doors. Doors shall be well fitted, self-closing and equipped with a three-point latch. 3404.3.2.1.4 Bottom. The bottom of the cabinet shall be liquid tight to a height of at least 2 inches (51 mm). 3404.3.2.2 Capacity. The combined total quantity of liquids in a cabinet shall not exceed 120 gallons (454 L). 3404.3.2.3 Number of storage cabinets. Not more than three storage cabinets shall be located in a single fire area, except that in a Group F occupancy, additional cabinets are allowed to be located in the same fire area if the additional cabinets (or groups of up to three cabinets) are separated from other cabinets or groups of cabinets by at least 100 feet (30 480 mm). |
| 05/04/2005 | VIOL - FLAMMABLE LIQUIDS | JLANGEJA | Violation | TFC 3404.3.2.1- Design and construction of liquid storage cabinets shall be in accordance with this section. See attachment A. |