Case: T05FR00415

Parcel: 12908105B


Addresses:

970 S CAMPBELL AV

Inspection Status: Violation

Inspection History: INSP - FULL

Date Description Inspector Results Comments
03/29/2005 INSP - FULL Violation 1). Currently wooden pallets are adjacent to building. Pallets shall be moved away from building at least 10 feet. If moved top adjacent tom property line the following Tucson Fire code must be met. TFC 304.1

315.3 Outside storage. Outside storage of combustible materials shall not be located within 10 feet (3048 mm) of a property line.
Exceptions:
1. The separation distance is allowed to be reduced to 3 feet (914 mm) for storage not exceeding 6 feet (1829 mm) in height.
2. The separation distance is allowed to be reduced when the fire code official determines that no hazard to the adjoining property exists.
03/29/2005 INSP - FULL Violation 2). Fire extinguisher shall be mounted in used battery storage. TFC 906.