Case Details

Status:

COMPLETE

Type:

INSPECTION

Entered Date:

03/29/2005

Applicant:

HARBOUR MICHAEL W & ROSETTA E JT/RS

Description:

inspection

Outstanding Inspections

Case Number: T05FR00415
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 2
End Date Description Inspector Results Comments
03/29/2005 INSP - FULL EGRIFFIN Violation 2). Fire extinguisher shall be mounted in used battery storage. TFC 906.
03/29/2005 INSP - FULL EGRIFFIN Violation 1). Currently wooden pallets are adjacent to building. Pallets shall be moved away from building at least 10 feet. If moved top adjacent tom property line the following Tucson Fire code must be met. TFC 304.1 315.3 Outside storage. Outside storage of combustible materials shall not be located within 10 feet (3048 mm) of a property line. Exceptions: 1. The separation distance is allowed to be reduced to 3 feet (914 mm) for storage not exceeding 6 feet (1829 mm) in height. 2. The separation distance is allowed to be reduced when the fire code official determines that no hazard to the adjoining property exists.

Completed Inspections

Case Status: COMPLETE
Case Number: T05FR00415
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
04/18/2005 COMPLIANCE EGRIFFIN Approved all approved