Case: T05FR00410

Parcel: 11104210Q

Inspection Status: Correction Required

Inspection History: VIOL - MEANS OF EGRESS

Date Description Inspector Results Comments
03/28/2005 VIOL - MEANS OF EGRESS Correction Required 1026.3 The exit signs at the west side and the south side sales floor exits shall be internally illuminated at all times.
03/28/2005 VIOL - MEANS OF EGRESS Correction Required 1026.5 The emergency lighting fixture located at the stairwell shall be repaired.
03/28/2005 VIOL - MEANS OF EGRESS Correction Required 1027.2 Required exit accesses shall be maintained free from obstructions. The exits at the west side of the salesfloor and at the northwest corner of the building shall have clear exit paths.
03/28/2005 VIOL - MEANS OF EGRESS Correction Required 1008.1.8 The exit at the west side of the sales floor shall be readily openable from the egress side without the use of a key.