End Date Description Inspector Results Comments
03/28/2005 VIOL - FIRE SERVICE FEATURES TKNAPP Correction Required 505.1 Address numbers shall be posted in accordance with Pima County address display requirements.
03/28/2005 VIOL - BUILDING SVCS & SYSTEMS TKNAPP Correction Required 605.3 A clear working space 36 inches deep and the width of the panel shall be provided in front electrical panels at west side of sales floor.
03/28/2005 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1008.1.8 The exit at the west side of the sales floor shall be readily openable from the egress side without the use of a key.
03/28/2005 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1026.3 The exit signs at the west side and the south side sales floor exits shall be internally illuminated at all times.
03/28/2005 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1026.5 The emergency lighting fixture located at the stairwell shall be repaired.
03/28/2005 VIOL - MEANS OF EGRESS TKNAPP Correction Required 1027.2 Required exit accesses shall be maintained free from obstructions. The exits at the west side of the salesfloor and at the northwest corner of the building shall have clear exit paths.

Completed Inspections

Case Status: COMPLETE
Case Number: T05FR00410
Case Description: INSPECTION
Total Completed Inspections - 1
End Date Description Inspector Results Comments
04/12/2005 INSP - FULL TKNAPP Approved