Inspection History Details
Inspection Status: Approved
Inspection History: VIOL - FIRE PROTECTION SYSTEMS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/24/2005 | VIOL - FIRE PROTECTION SYSTEMS | Approved | All Repairs made | |
| 02/03/2005 | VIOL - FIRE PROTECTION SYSTEMS | Violation | TFC 901.6 Fire protection systems. Fire sprinkler systems shall be maintain at all times. The following problems were found on your sprinkler system and need to repaired or replaced: 1.) Center of basement pendent head dent - Replace 2.) Ceiling tile missing behind reception desk - Replace 3.) Label main control valve and inspectors test valve. 4.) Replace missing sprinkler heads in sprinkler box. |