Case: T05FR00147

Parcel: 130140260


Addresses:

4082 E 22ND ST


Inspection Status: Correction Required

Inspection History: INSP - FULL

Case Number - T05FR00147

Inspection Description - INSP - FULL

Inspection Status - Correction Required

Date Description Inspector Results Comments
02/02/2005 INSP - FULL Correction Required Kid's room:
901.6 maintain proper sprinkler coverage
1008.1.9 repair or relace all missing or broken panic hardware
1011.2 all emergency back up lighting shall operate

Riser Room:
703.1maintain fire resistive construction

Spinning Ro0m
901.4 remove tape on sprinkler heads

Big Screens:
605.6 replace missing electrical cover plates (under)
901.4 Sprinkler coverage shall be extended to maintain coverage

Aerobics:
703.1 replace ceiling tile
605.6 replace cover plate
605.5 do not use extension cords as a substitute...

North Exit:
605.5 place a blank in electrical panel
901.6 fire extenguishers shall be properly mounted and serviced.