Case Details

Status:

COMPLETE

Type:

INSPECTION
Address:

Entered Date:

02/02/2005

Applicant:

RANDOLPH PLAZA LLC

Description:

fpi

Outstanding Inspections

Case Number: T05FR00147
Case Status: COMPLETE
Case Description: INSPECTION
Total Outstanding Inspections - 1
End Date Description Inspector Results Comments
02/02/2005 INSP - FULL JDAVIS Correction Required Kid's room: 901.6 maintain proper sprinkler coverage 1008.1.9 repair or relace all missing or broken panic hardware 1011.2 all emergency back up lighting shall operate Riser Room: 703.1maintain fire resistive construction Spinning Ro0m 901.4 remove tape on sprinkler heads Big Screens: 605.6 replace missing electrical cover plates (under) 901.4 Sprinkler coverage shall be extended to maintain coverage Aerobics: 703.1 replace ceiling tile 605.6 replace cover plate 605.5 do not use extension cords as a substitute... North Exit: 605.5 place a blank in electrical panel 901.6 fire extenguishers shall be properly mounted and serviced.