Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/09/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :*OK FINAL | |
| 12/23/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The service is not per code.| 210*NEED PERMANENT ADDRESS LABEL IDENTIFY PANEL DIRECTORY BONDING FOR GAS AND WATER NEEDS TO BE # 4 CU MIN HAVE OPEN L.B @ CARPORT NEED MAX 15 AMP BREAKER ON 126A KNOB & TUBE WIRING ( CLAD) GROUND FIRE PLACE OUTLET BOX GROUND J-BOX ENCLOSURE PROPERLY ( NO S?IF TAP SCREW) |
|
| 12/16/2005 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :*RECEIVED CHECK # 1057 FOR $ 108.00 AFTERHOURS INSPECTION OLD DISCONNECT NOT ALLOWED FOR JUNCTION BOX. USE A LISTED PRODUCT CONDUITS NOT TO HAVE MORE THAN 360 DEGREE IN A RUN OK TO CLEAR INCR. CALLED MAP ROOM 6:10PM PLEASE RECALL BY 12/21/05 |