Permit: T05EL02376

Parcel: 113092630


Addresses:

1102 E COPPER ST

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
01/09/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*OK FINAL
12/23/2005 ELECTRIC - FINAL Denied IVRS - Inspection :
The service is not per code.| 210*NEED PERMANENT ADDRESS LABEL
IDENTIFY PANEL DIRECTORY
BONDING FOR GAS AND WATER NEEDS TO BE # 4 CU MIN
HAVE OPEN L.B @ CARPORT
NEED MAX 15 AMP BREAKER ON 126A KNOB & TUBE WIRING ( CLAD)
GROUND FIRE PLACE OUTLET BOX
GROUND J-BOX ENCLOSURE PROPERLY ( NO S?IF TAP SCREW)
12/16/2005 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*RECEIVED CHECK # 1057 FOR $ 108.00 AFTERHOURS INSPECTION
OLD DISCONNECT NOT ALLOWED FOR JUNCTION BOX. USE A LISTED PRODUCT
CONDUITS NOT TO HAVE MORE THAN 360 DEGREE IN A RUN
OK TO CLEAR INCR. CALLED MAP ROOM 6:10PM PLEASE RECALL BY 12/21/05