Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/26/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1) CHANGE PERMIT DESCRIPTION TO SERVICE UPGRADE 2) INSTALL 2 GROUND RODS 6' MINIMUM APART 3) BOND WATER AND GAS PIPING 4) INSTALL BOND BUSHING AT TERMINATION WHEN USING RE-WASHERS AT PANEL 5) SUPPORT RISER CONDUIT WITHIN 3' OF PANEL-USE 1/4" BOLTS 6) CALLED LEFT MESSAGE TO APPLICANT |
|
| 10/21/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*SEE NOTES LAST INSPECTION. SEE 90.4, 110.3,230.79 C (NEC) |
|
| 10/20/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) YOU CANNOT UPGRADE THE EXISTING 60 AMP SERVICE BY REPLACING THE DISCONNECT WTIH A 100/125 AMP PANEL 2) UPGRADE THE SYSTEM WITH AN ALL IN ONE RATED AND LISTED FOR AMPERAGE OR REPLACE WITH NEW W/P 60 AMP DISCONNECT PER 110 NEC LISTING |
|
| 09/09/2005 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SERVICE OUTDATED-INDOOR RATED SERVICE DISCONNECT, UPDATE SERVICE OR REPLACE 60 AMP DISCONNECT WITH OUTDOOR RATED. DBL LUGGING NOT ALLOWED, EXPOSED ROMEX SHOULD BE IN CONDUIT 2) INSTALL SMOKE DETECTORS IN SLEEPING AREAS, DEVICE COVERS AND LIGHT FIXTURES |