Permit: T05EL00940

Parcel: 10711254A

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
11/23/2005 ELECTRIC - FINAL Approved IVRS - Inspection :*
09/10/2005 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) LABEL BREAKERS
2) PLEASE APPLY ANTI-OXIDE COMPOUND AND RETIGHTEN ALUMINIUM CONDUCTORS
3) REMOVE NM CONDUCTORS FROM DBL TAP AT BREAKER
4) ADDRESS TO BE 319 E. BLACKLIDGE DR. THIS IS WHERE METER IS LOCATED
5) PERMANENT METAL ADDRESS LABELS ARE NEEDED
6) PLEASE REPLACE MISSING COVER SCREWS