Permit: T05EL00531

Parcel: 107081190


Addresses:

732 W TIPTON DR

Inspection Status: Denied

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
03/24/2005 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999* 1) FRONT PORCH LIGHT FIXTURE TO BE REPLACED, WIRES CUT. 2) MIDDLE CARPORT FIXTURE HANGING ON WIRE. 3) WATER HEATER CIRCUIT- CONDUCTORS GOING INTO CIRCUIT BREAKER-BOTTOM ONE-BURNT COPPER & LOOSE-NEEDS TO BE CUT BACK RESTRIPPED & RE LANDED. 4) REPLACE BROKEN RECEPTACLE BY REAR DOOR INSIDE. 5) INSTALL ALL MISSING OR BROKEN RECEPTACLE COVERS. 6) LIGHT IN WASH ROOM NEEDS A J-BOX BEHIND IT AND TO BE INSTALLED. 7) RECEPTACLES SUCH AS IN LIVING ROOM CANNOT HAVE GROUNDS TIED TO NEUTRALS AND WHERE THERE ARE NO/ GROUNDS IN RECEPTACLES THEY MUST BE OF A TWO HOLE TYPE. 8) WATER HEATER J-BOX NEEDS COVER, THE WATER HEATER WIRING ALSO NEEDS COVER. 9) SMOKE DETECTORS REQUIRED IN BEDROOMS, BATTERY OK SEE LISTING FOR INSTALLATION INSTRUCTIONS ON LOCATIONS