Case: T05DV01278

Parcel: 134113180


Addresses:

808 S STUART PL

Inspection Status: Approved

Inspection History: INSP - INITIAL CODE ENFORCMENT

Date Description Inspector Results Comments
03/03/2006 INSP - INITIAL CODE ENFORCMENT Approved SITE INSPECTION: TENANT CINDY AT HOME WITH TWO CHILDREN.
MAIN SERVICE: DROP TO WEATHER HEAD APPEARS TO BE NOT AT PROPER HEIGHT, JUST ABOVE ROOF. 100 AMP MAIN SERVICE FUSE TYPE. WITH TWO SUB PANELS WORK WITHOUT PERMITS.
HAZARDOUS MODIFICATIONS TO SERVICE PANEL,
DOUBLE LUGGING ON LINE SIDE, FEEDING SUBPANEL AS NEUTRAL
TRIPPLE LUGGING ON LOADSIDE FEEDING TWO SEPERATE SUBPANELS
GROUND CONDUCTORS, MIXING COPPER AND ALUMINUM. ALSO DOUBLE LUGGING TO GROUND WITH SUB PANEL.
BOX IS WEATHERED AND WATER DAMAGED, RUSTING IN INTERIOR.
SUBPANEL 1ST, LIVE/HOT CONDUCTOR NO FUSES IN PANEL
LOAD SIDE CONDUCTORS MELTING, NOT SURE WHERE THEY FEAD
CONNECTION/ SCREW HOLD IN WIRE BARELY HOLDING WIRES. NO DEDICATED NUETRAL
SECOND SUB PANEL, FRIED WIRE, WEATHERED.
DOUBLE LUGGING ON LOADSIDE.
MISSING FUSES, NO GROUNDING DEDICATED NUETRALS
MISSING ROCK OUTS
DISCONNECT FRIED, NOT ABLE TO SAFELY DISCONNECT POWER

INTERIOR SUB PANEL; GROUND AND NEUTRAL BEING COMBINED.
MIXING ALUMINUM WITH COPPER SPLICING INSIDE OF SUBPANEL. BUSS BAR APPEARS TO BE LOOSE.

CARPORT SHED LIGHT BEING FED BY UNPROTECTED ROMEX
CARPORT LIGHT; HAZARDOUS UNPROTECTED ROMEX FEEDING LIGHT
OUTSIDE OUTLET NOT GFI PROTECTED. ETST SHOWS OPEN GROUND
CONDUCT IS LOOSE NOT PROPERLY SECURED TO WALL.

INTERIOR:
LIVING ROOM: BROKEN LIGHT SWITCH; SMOKE DETECTOR MISSING BATTERY NOT ABLE TO TEST.
OUTLETS ARE MIXED FROM 2 PRONG TO 3 PRONG OUTLESTS
A/C WALLMOUNT NOT HARDWIRED TENANT STATES IT DROPS REST OF HOME.
KITCHEN: OUTLETS TEST OF CABINET UNDER SINK OFF HINGES
PLUMBING: DRAIN LEAKING
STOVE: ELECTRIC BURNS RIGHT REAR NOT WORKING: HAZARDOUS ELECTRIC UNDER STOVE LOOTED
PANTRY MISSING DOOR. WAS EXTERIOR
LAUNDRYROOM: ADDED TO ORIGINAL DWELLING
OPEN GROUNDS THROUGHOUT LAUNDRY ROOM
1 COMPUTER ROOM WEST WALL OUTLET NOT WORKING OTHERS SHOW OPEN GROUND
2 KIDS ROOM: OPEN GROUND OTHERS THAT DO NOT WORK
3 ROOM SPARE 2 PRONG OUTLETS
HALLWAY BATHROOM, WENT NOT WORKING PROPERLY

HEATER AND HOT WATER HEATER
HWH DOES NOT HAVE PROPER PRESSURE RELIEF VALVE, WATER SPICKET.
HEATER; DIRTY NEEDS CLEANING, SERVICING, HEATER DOESN'T WORK
MASTER BEDROOM HAS NO GROUNDED OUTLETS
TENANT DAVID STATES HAS NO GROUNDED OUTLETS

PORCH: ROTTED WOOD, POST NOT ANCHORED.