Case: T05DV00439

Parcel: 13508006D


Addresses:

7440 E 22ND ST


Inspection Status: Correction Required

Inspection History: NPO - UNSECURED BUILD OR STRUC

Case Number - T05DV00439

Inspection Description - NPO - UNSECURED BUILD OR STRUC

Inspection Status - Correction Required

Date Description Inspector Results Comments
06/22/2005 NPO - UNSECURED BUILD OR STRUC Correction Required 6/21/05, VISITED SITE, TOOK PICTURES, INSP. GOODMAN ASST. UPON ARRIVAL FOUND 4 SEPERATE STRUCTURES, 7438-7444, WALKED EXTERIOR OF PROPERTY, NO ONE AROUND AT THIS TIME, EXTERIOR OF PROPERTY SHOWS GRASS STARTING TO OVER GROW, SOME AREAS HAS TRASH AND DEBRIS, NOT OVER ACCUMULATION, POOL AREA BARRIER FENCE IS DETERIORATING, SUPPORT POST RUSTED AND NOT WITHSTANDING ALL FORCES PLACED UPON THEM, RAILING CONNECTIONS RUSTED AND BREAKING AWAY FROM SUPPORTS, EAST SIDE OF BARRIER HAS BROKEN AWAY AND ALLOWING FOR PANELS TO BE PULLED OR PUSHED AND ALLOWS FOR MORE THAN REQUIRED 4" OPENINGS, WALKED ALL STRUCTURES 1ST AND 2ND FLOORS, KNOCKED ON DOORS AT LEASE ONE UNIT AT EACH END OF STRUCTURES ANSWERED ON BOTH FLOORS,
SOME UNITS ARE SECTION 8,
3,5,8,9,27,28,34,38,43,46
RESULTS ARE:
BUILDING 7438
DOWNSTAIRS HALLWAY ABIENT 89.5
UNIT 1 NO ANSWER
UNIT 6 VACANT AND UNSECURED AT THIS TIME
UNIT 5 NO ANSWER
UNIT 2 NO ANSWER
UNIT 4 NO ANSWER
UNIT 3: LIVING ROOM ABIENT TEMP 88
BEDROOM ABIENT 80
AIR FROM REGISTER 82, ALSO HAS FAN.
UPSTAIRS:
UNIT 9 NO ANSWER
UNIT 10: JUST MOVED IN 4 DAYS AGO, KITCHEN ABIENT 89
LIVING ROOM REGISTER TEMP 80
MASTER BEDROOM 78 AT REGISTER
RESIDENT WAS STATING UNIT WAS NOT READY FOR MOVE IN, TOILET DIRTY, TUB/SHOWER AREA TILES GROUT AND CAULKING CRACKED AND SEPERATED ALLOWING FOR WATER TO ENTER IN BEHIND AND DETERIORATE STRUCTURE WALLS.
MEDICINE CABINET MISSING DOOR.
UNIT 18: NO ANSWER
UNIT 13: NO ANSWER
UNIT 14: NO ANSWER
UNIT 17: NO ANSWER
UNIT 16: KITCHEN ABIENT TEMP 83.5
LIVING ROOM REGISTER TEMP 72, LIVING ROOM ABIENT 79
MASTER BEDROOM 72 AT REGISTER
BUILDING 7440
UNIT 19: NO ANSWER
UNIT 24: NO ANSWER
UNIT 23 VACANT AND UNSECURED AT THIS TIME
UNIT 20: KITCHEN AMBIENT 87, REGISTER 73
LIVING ROOM 82.5, REGISTER 73.5
UNIT 17 VACANT AND UNSECURED AT THIS TIME
UNIT 28: LIVING ROOM AMBIENT 84, REGISTER 74.5
MASTER BEDROOM AMBIENT 81, REGISTER 74
UNIT 26: LIVING ROOM AMBIENT 84, REGISTER 74.5 MIDDLE BEDROOM AMBIENT 79, REGISTER 73
UPSTAIRS:
UNIT 31: LIVING ROOM AMBIENT 89.5, REGISTER 78
MIDDLE BEDROOM AMBIENT 85, REGISTER 75
UNIT 34: KITCHEN AMBIENT 87, LIVING ROOM AMBIENT 87, REGISTER 75
MASTER BEDROOM AMBIENT 85, REGISTER 74
UNIT 33: KITCHEN AMBIENT 89, LIVING ROOM REGISTER 81
MASTER BEDROOM AMBIENT 91, REGISTER 81
UNIT 39: LIVING ROOM AMBIENT 86, REGISTER 75
MASTER BEDROOM 84, REGISTER 75
UNIT 37: LIVING ROOM 81.5, REGISTER 75
MASTER BEDROOM 81, REGISTER 75
UNIT 43: LIVING ROOM 88, REGISTER 78
MASTER BEDROOM 82.5, REGISTER 76
BATH TUB/SHOWER DIVERTER CONTINOUSLY LEAKS
UNIT 45: NO ANSWER
UNIT 46: NO ANSWER
ALL FIRE DOORS LOCATED ON ALL BUILDING BROKEN, DO NOT CLOSE PROPERLY, MISSING ALL PANIC HARDWARE, DO NOT MEET STANDARD REQUIRMENTS, WILL CALL TUCSON FIRE DEPT. FOR FOLLOW UP INSP. ON DOORS.
CHILLER DOES NOT EFFECTIVELY COOL DWELLINGS AS REQUIRED AT THIS TIME. ONLY HALF OF ONE CHILLER OPERATING. DOES NOT MEET REQUIRED REQUIREMENTS.
WHILE ON SITE ORACLE CONTROLS SHOWED UP WORKING ON BROKEN COMPRESSOR, TALKED WITH CASEY (TECH) WHO WAS IN PROCESS OF DISASSEMBLING CHILLER WENT OVER ISSUES HE STATED WOULD NEED TO TALK TO MO, RECIEVED CONTACT NUMBER, CASEY ALSO STATED HE WAS IN ROUTE TO PROPERTY, WAITED, MO SHOWED UP ON SITE, WENT OVER ISSUES WITH MO, HE STATED THAT HE WAS ACTING AS A BROKER BETWEEN BOTH CURRENT OWNER AND NEW OWNER, FINALLY BOTH PARTIES AGREED TO A SOLUTION, MONEY ISSUES, AT THIS TIME THERE ARE 2 CHILLERS ON SITE, NORTH CHILLER AND SOUTH CHILLER, SOUTH CHILLER COMPLETELY DOWN, DOES NOT OPERATE AT ALL, NORTH CHILLER HAS 2 COMPRESSORS, ONLY ONE OPERATES AT THIS TIME, DECISION IS TO REPLACE BROKEN COMPRESSOR, ALSO TO REMOVE SOUTH CHILLER AND REPLACE WITH TEMPORARY RENTAL CHILLER, AS TALKING WITH MO I EXPLAINED I NEEDED TIME FRAMES AND AVAILABILTY OF BOTH PARTS, MO STATED HE WOULD CHECK ON BOTH AND CALL ME IN APPOX 1 HR. HE DONE THIS,
MO CALLED ME BACK AND STATED THAT AS WE SPEAK COMPRESSOR IS BEING TRANSPORTED TO PROPERTY, ALSO RENTAL CHILLER IS BEING LOADED ON TRUCK FOR DELIVERY, PROCESS IN PLACE, AT THIS TIME CHILLER IS ONLY PRODUCING ABOUT 50% OF CAPICITY, MO STATED THAT ONCE THE NEW COMPRESSOR ARRIVES AND IS INSTALLED THIS WILL BRING UP EFFICIENCY TO APPOX. 70% THIS SHOULD BE DONE WEDNESDAY 6/22, THEN WILL DO REPLACEMENT OF SOUTH CHILLER WITH RENTAL AND THIS WILL BRING UP EFFICIENCY TO 90 TO 95%, THIS SHOULD BE DONE THURSDAY 6/23, LOOKING AT BRINGING SITUATION UNDER CONTROL WITHIN 48 HOURS FOR COOLING, CALLED KEN McDONALD AT SECTION 8 APPRISED KEN OF ALL ISSUES, TIME FRAMES AND PROCESS MOVING FORWARD, WILL BE DONG FOLLOWS UPS WITH MO ON ALL PROGRESS.