Permit: T05CM06452

Parcel: 10820020A


Addresses:

4084 N 1ST AV #01

Inspection Status: Not ready for Inspection

Inspection History: SITE - SEWER

Date Description Inspector Results Comments
01/20/2006 SITE - SEWER Not ready for Inspection IVRS - Inspection :*EXCEPT FOR THE TWO WAY CLEAN OUT, WHERE THE BLDG. DRAIN & BLDG. SEWER CONNECT, CLEAN OUTS SHALL OPEN IN THE DIRECTION OF FLOW. CLEAN OUTS ARE REQUIRED WHEN YOU EXCEED ONE HUNDRED FEET, AND HWN YOU EXCEED 135 DEGREE CHANGE OF DIRECTION. A DIRECTIONAL CLEAN OUT IS REQUIRED AT THE PROPERTY LINE-PER PCWWM DETAIL 104. TRACER WIRE IS REQUIRED PER DETAIL 104 PCWWM AND HOUSE BILL 2256
01/20/2006 SITE - SEWER Approved IVRS - Inspection :*
1. 4" SEWER FROM TAP AT MAIN INCLUDING DIRECTIONAL CLEAN OUT AT P.L AND ALL THE WAY TO WITHIN TEN FEET FROM THE BLDG 3 PLACES - OK
2. GREEN TRACER WIRE INSTALLED PER H.B. 2256 AND PCWWM DETAIL #4
3. OK TO COVER