Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
Permit Number - T05CM06452
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/23/2006 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
07/18/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. BOXES MORE THAN 1/4" IN NON-COMBUSTIBLE OR FLUSH INCOMPUSTIBLES TO USE AN APPROVED EXTENDER RING 314.20 2. TIGHTEN LOOSE FITTINGS AT FAN COIL 3. TIGHTEN LOOSE FITTING AT WATER HEATER & PROVIDE DISCONNECTING MEANS. 4. INSTALL ALL STRANDS UNDER GROUND SCREW OR USE A TERMINAL END JUNCTION BOX - FAN COIL. 5. MISSING LIGHT FIXTURES 6. INSTALL ALL STRANDS UNDER TERMINAL STRIP LUG AT PANEL. 7. IDENTIFY A/C DISCONNECTING MEANS 8. SUPPORT CARFLEX FOR FAN COIL. |
|
06/29/2006 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* |