Permit: T05CM06452

Parcel: 10820020A


Addresses:

4084 N 1ST AV #01

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
07/23/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
07/18/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. BOXES MORE THAN 1/4" IN NON-COMBUSTIBLE OR FLUSH INCOMPUSTIBLES TO USE AN APPROVED EXTENDER RING 314.20
2. TIGHTEN LOOSE FITTINGS AT FAN COIL
3. TIGHTEN LOOSE FITTING AT WATER HEATER & PROVIDE DISCONNECTING MEANS.
4. INSTALL ALL STRANDS UNDER GROUND SCREW OR USE A TERMINAL END JUNCTION BOX - FAN COIL.
5. MISSING LIGHT FIXTURES
6. INSTALL ALL STRANDS UNDER TERMINAL STRIP LUG AT PANEL.
7. IDENTIFY A/C DISCONNECTING MEANS
8. SUPPORT CARFLEX FOR FAN COIL.
06/29/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*