Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/06/2006 | PLUMBING - ABOVE CEILING | Approved | IVRS - Inspection :* PIPING IN WALLS AND ABOVE CEILING IS OK CLOSET FLANGES ARE NOT. ABS TO PVC TRANSITION GLUE IS FOR USE OUTSIDE BUILDING ONLY. A 3" FLANGE SHALL NOT BE USED INSIDE 4" PIPE. |
|
| 06/01/2006 | PLUMBING - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* |