Permit: T05CM06362

Parcel: 110121360

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
11/15/2006 ELECTRIC - FINAL Approved IVRS - Inspection :*
08/31/2006 ELECTRIC - FINAL Partial Approval
08/25/2006 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. LABEL WATER HEATER DISCONNECTING SWITCH
2. BOXES MORE THAN 1/4" FROM BOX TO SURFACE NEED AN APPROVED EXTENDER RING.
3. EMERGENCY EXITS TO BE ON CIRCUIT FOR AREA SERVED 700.12
4. LIGHTING DIFFERENT THAN PLANS PLEASE REVISE
5. IDENTIFY UNITS.