Permit: T05CM05902

Parcel: 129110800


Addresses:

1025 E 24TH ST #01

Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Date Description Inspector Results Comments
05/31/2006 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection :*
12/09/2005 PLUMBING - ROUGH, SOIL Partial Approval IVRS - Inspection :*
WASTE IN BUILDING OK - CALL FOR WRAPS BEFORE CONCRETE WATER PIPE TO BE ON PLAN - CLEANOUTS
12/07/2005 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. TEST WYG ON BUILDING SEWER MUST BE INSTALLED IN THE CORRECT DIRECTION OF FLOW.
2. CHECK GRADE - 2% SLOPE REQUIRED ON HORIZONTAL WASTE PIPING.
3. SHADE/SUPPORT ALL SECTIONS OF PIPING - LEAVE FITTINGS EXPOSED TO CHECK FOR LEAKS.
4. WATER TEST NOT HOLDING AT 10' HEAD
5. WATER PIPING NOT ACCORDING TO PRINT