Permit: T05CM05898

Parcel: 125121110

Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Permit Number - T05CM05898

Inspection Description - PLUMBING - ROUGH, SOIL

Inspection Status - Approved

Date Description Inspector Results Comments
12/12/2005 PLUMBING - ROUGH, SOIL Approved IVRS - Inspection :*
12/07/2005 PLUMBING - ROUGH, SOIL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. SHALL PROVIDE A WATER TEST ON DWV SYSTEM ALL THE WAY TO THE TOP OF VENT THRU ROOF.
2. SHALL PROVIDE L-SWEEPS FOR ALL VERTICAL TO HORIZONTAL DRAINAGE.
3. SHALL PROVIDE APPROVED HANGERS FOR HORIZONTAL VENT ABOVE CEILING.
4. SHALL REMOVE FERNCO COUPLINGS AT EXISTING BUILDING DRAIN AND PROVIDE SHIELDED MISSION COUPLINGS.
5. SHALL LOCATE THE RE VENT FOR LAV & SINK MIN 6" ABOVE THE FLOOD RIM LEVEL.
6. SHALL LOCATE C.O. ABOVE THE WATER CLOSET TANK & GRAP BARS FOR MIN OF 18" FRONTAL CLEARANCE.