Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
Permit Number - T05CM05898
Inspection Description - ELECTRIC - ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/28/2005 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
12/27/2005 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* | |
12/08/2005 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
12/06/2005 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245*INSTALL SLACK WIRES ON CEILING FIXTURES AND BATH FAN, SCREW OR CLIP TO CEILING GRID SECURE MC TERMINATIONS WITHIN 12" OF J-BOX INSTALL K.O BLANKS AND COVER PLATES ON AL J-BOX'S IN CEILING. IDENTIFY ALTERD CKT'S IN PANEL DIRECTORY. |