Permit: T05CM05879

Parcel: 141148150


Addresses:

9050 E VALENCIA RD


Inspection Status: Approved

Inspection History: MECHANICAL - ABOVE CEILING

Permit Number - T05CM05879

Inspection Description - MECHANICAL - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
06/28/2006 MECHANICAL - ABOVE CEILING Approved IVRS - Inspection :*
06/22/2006 MECHANICAL - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
06/19/2006 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
CHECKED GREASE DUCTS. OK TO PROCEED W/FIRE WRAP AND CLEAN OUTS.
06/14/2006 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
06/05/2006 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
FIRE WRAP OK
PROVIDE DOUBLE WALL VENT PIPE ON DISHWASHER.
OK FOR CEILING TILES BAKERY.
06/02/2006 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
PARTIAL ABOVE CEILING IN BAKERY. OK CEILING TILES WEST SIDE. PARTIAL TILES ON EAST SIDE.
06/01/2006 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
05/31/2006 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
SUSPENDED ROUGH DUCT ABOVE BAKERY OK TO INSULATE.
CHECKED WELDS ON GREASE DUCT UPPER 10' ONLY. OK TO START FIRE WRAP.
04/27/2006 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
CHECKED RETURN DUCT NEXT TO MEAT DEPT.
OK TO INSULATE ALL DUCTING FROM THIS POINT ON.
04/21/2006 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
CHECKED DUCT CONNECTIONS TO PHARMACY OK TO INSULATE
STILL NEED TO SEE CONDENSATE. IDENTIFY A/C UNIT DISCONNECT WITH PANEL & CIRCUIT NUMBERS. PROVIDE ROOF JACKS AT ROOF PENETRATIONS. PROVIDE CONDENSATE DRAIN. OK TO OCCUPY PHARMACY.
04/11/2006 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
SUSPENDED ROUGH DUCT ABOVE PHARMACY OK TO SHEETROCK.
WILL CHECK CONDENSATE & CONNECTIONS ON NEXT VISIT.
04/07/2006 MECHANICAL - ABOVE CEILING Partial Approval IVRS - Inspection :*
SUPPLY DUCT TO CASH OFFICE OK TO INSULATE.
SUPPLY DUCT TO FLORAL DEPT. OK TO INSULATE.